Description du produit
The double channel VEGATRENN 142 is used for galvanic separation, intrinsically safe power supply as well as signal transmission of Ex-approved 4 … 20 mA sensors in hazardous areas. The separate power supply ensures a reliable measured value transmission. VEGATRENN 142 is used in all industries als with Ex applications. The VEGATRENN 142 is suitable for bidirectional transmission of HART signals. The HART signal can be picked off via the HART communication sockets integrated in the front or the terminals. The complete HART permeability allows complete access to the sensor settings.
Caractéristiques générales
| Caractéristique | Valeur |
|---|---|
| Alimentation | 4 à 20 mA |
| Alimentation auxiliaire (V DC) | 20.4-34.1 |
| Bornes détachables codées | Oui |
| Montage | rail DIN |
| Nombre de voies | 2 |
| Plage de mesure | jusqu'à 30 m |
| Poids | 1,2 kg |
| Précision de mesure | ±2 mm |
| Pression de procédé maximale | 16 bar |
| Prise HART intégrée | Oui |
| Séparateur actif | Oui |
| Séparateur Ex universel | Oui (usage en zone Ex optionnel) |
| Séparation galvanique | Oui |
| Température ambiante | -20 °C à +60 °C |
| Température de fonctionnement | -40 °C à +80 °C |
| Transmission HART | bidirectionnelle |